1998-08-12 Engineering First Plan Reivew 08/12/1998 14:11 612-497-49138 JOINT POVERS PAGE 12 "".lLlC:/i!lc! !+ G~ 6 ~~!J UllL1DI EMllAiII.~ For/7Wl1y MSA w.jll~[;"Jr,t';' ~n,I""" I ~^r.J.t'id ~ ~rQl"'W", Compat)~y .-.J OON~~~~IN(:JI ENGjNE~i ' ~lYJy 21, '1~91' File: 8Q4.ClOJ Ms. Donn. K'pka Joint Powers Water SQard P.O. Box 10 Albertvile, MN 65301 RE; KARSTON COVE ADOITION TO ceDAR CREEK NORTM FIRST PLAN REVIEW eelr M.. Kipka: We have completed our ...Vlew of the plans IUbmittecf on July 8, 1998 for t'" . .' ~,(',v" . <'JIrtf. .~ project, and offer the foHowing comment,; · The wsterm.in on thli projeot is a continuatlon of the watermaln for the Cedar Creek North develoPment. As such, It extends the temponery dead end watermlin of that project. in addltlcn to the 3.300 feet contained in thlt proltd, !hie plan calls for the addition of 700 feet of tempOrary dead end Mten'n8in. At. this time, no definite schedule for lOoping thi$ line bIck to eXi$ting wet_.," in the City of AlbertvtUe he, been provided. ",. r..olution of this i'5ue is a poiie)' qUMtton for the Board to consider. . · The plans call for buttwfty v.Iv.. at all location. on the 12Jjnoh diameter watermain where valveli Ir. needed. .,Joint Powenl Standards for waterm.in conliltrlJctio" require gate valve. . on 12 inch dl;wneter Ind underwatennain (Sectfon 2.C,). "T"h4J correct valve type should be ,peoified in the r*ns. · . There IS leu thin 18 inchQ sepa~on between the Mnltary sewer and 8 inch watermain at Statton" 2+06 and 5+94 of Private Drive el~k 1. The detail showing lowering of Mter 6ervices in C8M of Conflict, .hould be moctified to apply to w.termsin conflicts with tne S8nltary sewer alto. · The 8-inch diameter .ermain. crossing the &anltllry sewer .t StBtion 6~2 on Karstan Avenue doe, not apPear to. have the required 18-Inch dearance. In addition. the sanitary sewer lJ8rvice fine' at Station 5+52 on Karston Avenue doe. not have tt18 required 18-lnch separation It ita Ql'OIaini point with the 12 Inch wat.rmlin. These ClOnflic:ts should be gorrectltd, such as by lowering of the waterma". at thi, location. · Th, wllttermain in much of this development i. .hown to be out$ide of street rJght-g.fMWay. but the loO'ttion of utility euements'i. not ,hown. I" one location, at Lots 19 , 20, 810ck 1, the O:~\HOo2003.ju1 '~e energy Part DrIve · St. PQut. MN 55108 · 81V644-4S89 faK 612/6404-944e toll free8H/3e8.4389 TOTAL P.02 138/12/1998 14:11 612-497-49138 JOINT POI,.oERS PAGE 13 Ms. Donna Kipka July 20, 1998 Page Two watermain is shown to. cross townhouse lots. Information on the locations of utility easements must be provided for review to assure compliance with Joint Powers' requirements for watennain location. · The plans show water service line curb stops to be located within 3 feet of driVeways at Lots 3,4, & 7, Block 3, and Lots 5 & 17, Block 1. These services should be moved so that the curb stops are at least 3 feet from the edge of the driveways. · The plans appear to show the curb stDp!j; Qf1 the lot property lines. Thera is no note or detail on thepfan$ shO\Ning' the Board's requirement that curb stops be iOiatedat least 1 foot from lot property boundaries or easement boundaries. A note should be added to the plans to make this requirement claar to the contractor, in addition to submitting a plat showing the easements as required above. · The specifications for this project contain standard details for installing water services for both Joint Powers Water Board and the City of Albertville, and these standards are in conflict. A note should be added to the plans referencing the Joint Powers Standards and details in the specifications, and stating the Joint Powers standards always apply where more stringent. . · Board Design Standards require hydrants at the end of dead-ends for flUShing purposes. A temporary hydrant should be added to the end of the 12" stub ending north of Co. Hwy. 37. Based on the items listed above, we do not recommend approval of the plans for Karston Cove until corrections are made. If you have any questions, please call me. Sincerely, Howard R. Green Company n-.t, !},~ Randy D. Surbaugh, P.E. RDS:mw Cc: Francis D. Hagen. II PE Westwood Professional Services 104 Marty Drive, Suite 3 Buffalo, MN 55313. O:\proJ18G4480J\4eO-2003.jul Howard R. Green Company CONSULTING ENGINEERS